FREE NEC 220 TOOL

Electrical Load Calculator

Calculate total connected load, demand load, and recommended service panel size for residential and commercial installations.

SECTION 1 โ€” GENERAL LIGHTING & RECEPTACLES

NEC 220.12 โ€” 3 VA per square foot of living area (excludes garages, open porches, unfinished spaces).

Finished floor area only โ€” do not include garage or unfinished basement.
6,000 VA
Square feet ร— 3 VA = lighting & receptacle load

SECTION 2 โ€” SMALL APPLIANCE, LAUNDRY & BATHROOM CIRCUITS

NEC 220.52 โ€” Fixed 1,500 VA per circuit. Small appliance: minimum 2 circuits. Laundry: minimum 1 circuit. Bathroom: 1,500 VA.

3,000 VA
1,500 VA ร— number of circuits
1,500 VA
1,500 VA ร— number of laundry circuits
1,500 VA
1,500 VA ร— number of bathroom circuits

SECTION 3 โ€” INDIVIDUAL APPLIANCES

Enter nameplate VA or watts for each appliance. NEC demand factors apply automatically. Leave blank or enter 0 to omit.

โšก LOAD CALCULATION RESULTS (NEC STANDARD METHOD)
LOAD BREAKDOWN

COMMERCIAL LOAD LIST โ€” NEC 220.40

Add each load below. Enter amps or watts per unit. The calculator converts to VA and applies your demand factor. For 3-phase loads, VA = V ร— A ร— 1.732.

Description Voltage Phase Entry Mode Value Qty / DF%
โšก COMMERCIAL LOAD CALCULATION RESULTS
ITEMIZED LOAD TABLE

NEC REFERENCE TABLES

Use the tables below to look up standard demand factors and typical appliance ratings when nameplate data is unavailable.

TABLE 1 โ€” Residential General Lighting Demand Factors (NEC 220.42)
Portion of General Load Demand Factor Applied To
First 3,000 VA100%General lighting + small appliance + laundry totals
3,001 VA to 120,000 VA35%Remainder of general load
Above 120,000 VA25%High-load dwellings
First 10,000 VA (Standard Method used here)100%Simplified standard method per NEC 220.82
Remainder above 10,000 VA (Standard Method)40%Applied to general + small appliance + laundry
TABLE 2 โ€” NEC 220.55 Electric Cooking Equipment Demand Factors
Nameplate Rating (kW) Demand Factor / Rule
Up to 1.75 kWUse nameplate rating
1.76 kW to 8.75 kW80% of nameplate
Over 8.75 kW (single unit)8,000 W demand + 40% of amount over 8,750 W
Household electric dryer5,000 W minimum or nameplate, whichever is larger (NEC 220.54)
TABLE 3 โ€” Typical Residential Appliance VA Ratings
Appliance Typical VA Range NEC Notes
Central A/C (3-ton)4,000โ€“6,000 VAUse nameplate; include in largest motor calc
Heat Pump (3-ton)3,500โ€“5,500 VAUse nameplate or NEC Table 430.248/250
Electric Water Heater4,500โ€“5,500 VAUse nameplate rating at 100%
Electric Range / Oven8,000โ€“14,000 VANEC 220.55 demand applies
Electric Clothes Dryer5,000โ€“6,000 VANEC 220.54: 5,000 VA minimum
Dishwasher1,200โ€“1,800 VAUse nameplate; 100% demand
Garbage Disposal700โ€“1,200 VAUse nameplate; 100% demand
Microwave (built-in)1,200โ€“1,800 VAUse nameplate; 100% demand
EV Charger (Level 2, 32A)7,680 VA240V ร— 32A; 100% demand per NEC 625
EV Charger (Level 2, 48A)11,520 VA240V ร— 48A; 100% demand per NEC 625
Hot Tub / Spa4,000โ€“7,500 VANEC 680 applies; use nameplate
Pool Pump1,500โ€“3,000 VANEC 680 applies; use nameplate