Electrical Motor Calculator

Calculate FLA, horsepower, kVA, NEC breaker size, and wire gauge for single-phase and three-phase motors.

Calculate Full Load Amps (FLA)

Typical: 85–95%. Check motor nameplate.
Typical 3Ø: 0.80–0.90. See nameplate.
⚡ RESULTS

Calculate Motor Horsepower

⚡ RESULTS

Calculate Apparent Power (kVA)

⚡ RESULTS

NEC Circuit Breaker Sizing (NEC 430.52)

From nameplate or calculated above.
⚡ RESULTS

NEC Motor FLA Reference — 460V/480V Three-Phase (Table 430.250)

HP460V FLA (A)480V FLA (A)Min. Conductor (A)Max. Breaker Size
½1.11.01.43A
¾1.61.52.04A
12.12.02.66A
3.02.93.758A
23.43.34.259A
34.84.66.012A
57.67.39.520A
1110.513.7528A
101413.417.535A
152120.126.2553A
202725.833.7568A
253432.542.585A
304038.350100A
405249.765130A
506562.181.25163A
607773.696.25193A
759691.7120240A
100124118.5155310A
125156149.1195390A
150180172.0225450A
200240229.4300600A

Copper Wire Size vs. Ampacity (NEC 310.15, 75°C)

AWG / MCMAmpacity (A)Typical Motor HP (460V 3Ø)
14 AWG15AUp to 1 HP
12 AWG20AUp to 1½ HP
10 AWG30AUp to 3 HP
8 AWG50AUp to 5 HP
6 AWG65AUp to 7½ HP
4 AWG85AUp to 10 HP
3 AWG100AUp to 15 HP
2 AWG115AUp to 15 HP
1 AWG130AUp to 20 HP
1/0 AWG150AUp to 25 HP
2/0 AWG175AUp to 30 HP
3/0 AWG200AUp to 40 HP
4/0 AWG230AUp to 50 HP
250 MCM255AUp to 60 HP
350 MCM310AUp to 75 HP
500 MCM380AUp to 100 HP